Mk3 - Class 0.2S / Class 0.5S Energy Meter
The Mk3 revenue meter is high accuracy meter with extensive in built features for the deregulated market.
It is available as a CT connected unit ( 1A or 5A) . Each meter is capable of four-quadrant measurement of one three-phase load. It conforms to IEC 60687 and can be purchased as a Class 0.2S or Class 0.5S accuracy meter. The Mk3 includes support for optical fibre meter to meter communications; and support for quality of supply features such as harmonic analysis, voltage sag and swell logging.
• Four quadrant energy measurement
• Time Of Use
• Load profile
• Pulse inputs / outputs
• CT only
• High accuracy
• Remote reading
• Waveform capture
• Sag and swell analysis ( half cycle resolution)
• Quality of supply ( On board harmonic analysis)
• Voltages :
Nominal : 57 to 240V ( Phase to Neutral)
Min. to Max. : 45 to 290V
Burden : < 10VA / phase @ Vn ( 3 Phase)
( as per IEC62053-61)
• Auxiliary Supply :
110V ( others available on special order)
• Current :
Nominal : 1 A ( C.T.) | 5 A ( C.T.)
Range Standard : 0.05A - 1.2A | 0.25A - 6A
Range Extended : 0.05A-4A | 0.25A-20A
Short Time Over-Current : 20 times the Imax for 0.5 second
Starting Current : < 0.10% of In ( Ib for WC)
Burden : < 0.5VA / phase
• Measurement Mode :
Single Phase ( 3 circuits)
3 Phase 3 Wire
3 Phase 4 Wire
• Pulse Outputs :
Voltage, Current, Pulse Width, Polarity
• Pulse Inputs :
Voltage
• Temperature Range
Operating : -10° C to + 60° C
Storage : -25° C to + 70° C
• Time Keeping
Accuracy( internal) ± 30 sec / month
Backup Time : 2 years without power
Backup Type : Lithium Battery
• Data Storage ( configuration and TOU Load Survey) :
FlashRAM, indefinite storage period
Battery backed up RAM
• Communications :
Local : ANSI Type 2 Optical ( standard) or FLAG™ ( IEC 1107) ( option)
Remote : Isolated RS485 or RS232 ( DB9 Connector)